Available Services |
|
 |
|
 |
Contact Closure
|
 |
For single channel applications, the FOT-CC and FOR-CC Fiber Optic Transmitter and Receiver provide point-to-point contact closure information over a single fiber optic cable.
For multi-channel applications, the EOTec 2000 fiber optic Multi-Channel Contact Closure transceiver modules are used to convert up to 10 contact closure inputs (switches, relays, etc.) into fiber optic signals for transmission over a single fiber optic link. |
 |
 |
EOTec Multi-Channel Contact Closure (MCCC) |

|
Overview
Introducing NSPI’s latest Multi-Channel Contact Closure models, now more robust than ever and with the latest certifications, including CE; Class I Division 2 Groups A, B, C, D for the US and Canada; and ATEX Zone-2, Category-3.
The EOTec fiber optic Multi-Channel Contact Closure transceiver modules for Safety-Shut Down applications are used to convert up to ten contact closure inputs into fiber optic signals for transmission over a single fiber optic link. These units are commonly used for remote transmission over long distances (up to 16 miles), transmission through hazardous areas and alarm event triggering.
Applications for this device include long distance transmissions, lightning prone areas, transmissions through hazardous areas and Safety-Shut Down applications.
Cost effective signal multiplexing without a PLC!
Each transceiver module includes two contact closure inputs and is capable of driving up to ten inputs by cascading additional dual channel input modules. A de-pluggable screw terminal on the bottom of the module is provided for connection to the input signal. An integrated backplane allows for communications between modules with no external inter-modular connection.
Flexible design for greater output driving capacity.
Each transceiver has a single optical port for use with multi-mode or single mode optical fiber with transmissions at 850 nm or 1300 nm using industrialized ST/SMA connectors. SPDT Form C relay outputs are provided for each channel capable of driving resistive loads with a maximum switching power of 120W, 250VA, and maximum switching current of 4A DC, AC. |
Features of Ultra Electronics, NSPI modular Multi-Channel Contact Closure (MCCC)
- Suitable for critical Safety Shut-Down applications
- Transmits from 1 to 10 Contact Closure signals over one fiber
- Compatible with multi-mode or single mode optical fiber
- De-pluggable screw terminals for all wire connections
- Integrated backplane with no external inter-modular connections
- Visible status LED’s for power, TX/RX and channel inputs
- Fail-Safe relay operation
- Accepts our standard power supplies
- Available with dual redundant, hot swappable power supplies
- Suitable for mounting on standard 35 mm DIN rail
- Operating range of –40 °C to 85 °C, 0-95% RH (non-condensing)
- Dimensions (each module): 22.5 mm w x 99 mm h x 114 mm d
Regulatory certifications
- CE
- Class I, Division 2, Groups A, B, C, D for the US and Canada
- ATEX, Zone-2, Category-3
|
Power requirements |
7.5 VDC via the BUS interconnections (from any EOTec 2000 power supply module)or 12 to 30VDC
@ 400mA, via a pluggable, screw terminal block on the CC-T/CC-R module |
Relay contact output |
SPDT Form C relay, via pluggable screw terminal, 12 to 24 AWG(0.5-2.4mm) Cage-Clamp
60W, 125VA, maximum switching power
220VDC, 250VAC, maximum switching voltage
2A switching, 3A carry, maximum current
100,000,000 cycles, minimum operational life |
Contact Closure input |
External Dry contacts connected via pluggable, screw terminal blocks
Accepts 12 to 24 AWG, 5VDC @ 1.4mA min. contact rating, 1K ohm max. resistance |
LED status indicators |
Power On Green, Ch. A Relay energized/input contact closed Green, Ch. B Relay
energized/contact input closed Green, Fiber Transmit – Amber |
Data update rate |
15mS regardless of the number of channels utilized |
Ambient conditions |
-40°C to 85°C Operational |
|
MCCC Fiber Optic Transmitters:
Model |
Description |
Optical Dynamic Range |
Input/Output type |
Fiber connector |
CC-TM85 |
2-Channel, 850 nm, Multi-mode, Transmitter |
12 dB |
Dry Contact Input |
ST |
CC-TM13 |
2-Channel, 1300 nm, Multi-mode, Transmitter |
12 dB |
Dry Contact Input |
ST |
CC-TM85H |
2-Channel, 850 nm, Multi-mode, transmitter |
17 dB |
Dry Contact Input |
ST |
CC-TS13 |
2-Channel, 1300 nm, Single-mode, transmitter |
10 dB |
Dry Contact Input |
ST |
CC-TS13H |
2-Channel, 1300 nm, Single-mode, transmitter |
16 dB |
Dry Contact Input |
ST |
|
MCCC Fiber Optic Receivers:
Model |
Description |
Input/Output type |
Fiber connector |
CC-RM85 |
2-Channel, 850 nm, Multi-mode, receiver |
Form C relay output |
ST |
CC-RX13 |
2-Channel, 1300 nm, Multi-mode or Single-mode, receiver |
Form C relay uutput |
ST |
|
MCCC Input/Output Modules:
Model |
Description |
Input/Output type |
Fiber connector |
CC-I |
2-Channel, 850 nm, input module |
Dry contact input |
N/A |
CC-O |
2-Channel, output module |
Form C relay output |
N/A |
|
MCCC sower supply options:
Model |
Description |
2A06 |
Power supply, 85 to 240VAC, 50/60Hz, or 85 to 140VDC |
2A16 |
Power supply, 85 to 240VAC, 50/60Hz, or 85 to 140VDC, w/ diagnostics |
2A08 |
Power supply, 24VDC |
2A8 |
Power supply, 24VDC, w/ diagnostics |
|
Application diagram:

|
|
|
 |
EOTec 2000 Multi-Channel Contact Closure (MCCC) *Legacy |

|
This model has been updated and replaced with the new Multi-Channel Contact Closure models, which now carry a variety of certifications and should be used in new applications. The EOTec 2000 line is still available should you need replacement parts for existing installations. Please contact us to purchase, or if you have any questions. |
Overview
The EOTec 2000 fiber optic Multi-Channel Contact Closure transceiver modules for Safety-Shut Down applications are used to convert up to ten contact closure inputs into fiber optic signals for transmission over a single fiber optic link. These units are commonly used for remote transmission over long distances (up to 16 miles), transmission through hazardous areas and alarm event triggering.
Applications for this device include long distance transmissions, lightning prone areas, transmissions through hazardous areas and Safety-Shut Down applications.
Cost Effective Signal Multiplexing without a PLC!
Each transceiver module includes two contact closure inputs and is capable of driving up to ten inputs by cascading additional dual channel input modules. A de-pluggable screw terminal on the bottom of the module is provided for connection to the input signal. An integrated backplane allows for communications between modules with no external inter-modular connection.
Flexible design for greater output driving capacity.
Each transceiver has a single optical port for use with multi-mode or single mode optical fiber with transmissions at 850 nm or 1300 nm using industrialized ST/SMA connectors. SPDT Form C relay outputs are provided for each channel capable of driving resistive loads with a maximum switching power of 120W, 250VA, and maximum switching current of 4A DC, AC. |
Features of Ultra Electronics, NSPI modular Multi-Channel Contact Closure (MCCC)
- Suitable for critical Safety Shut-Down applications
- Transmits from 1 to 10 Contact Closure signals over one fiber
- Compatible with multi-mode or single mode optical fiber
- De-pluggable screw terminals for all wire connections
- Integrated backplane with no external inter-modular connections
- Visible status LED’s for power, TX/RX and channel inputs
- Fail-Safe relay operation
- Accepts our standard power supplies
- Available with dual redundant, hot swappable power supplies
- Suitable for mounting on standard 35 mm DIN rail
- Operating range of –40 °C to 85 °C, 0-90% RH (non-condensing)
- Dimensions (each module): 22.5 mm w x 99 mm h x 114 mm d
|
Selection Guide:
MCCC Fiber Optic Transmitters:
Legacy model |
New model |
Description |
2S07 |
CC-TM85 |
Transmitter Module, 2-Ch, ST, 850nm, MM |
2S09 |
CC-TM13 |
Transmitter Module, 2-Ch, ST, 1300nm, MM |
2S10 |
CC-TM85H |
Transmitter Module, 2-Ch, ST, 850nm, MM, Hi-Powered |
2S36 |
CC-TS13 |
Transmitter Module, 2-Ch, ST, 1300nm, SM, Std-power |
2S46 |
CC-T13H |
Transmitter Module, 2-Ch, ST, 1300nm, SM, Hi-powered |
|
MCCC Fiber Optic Receivers:
Legacy model |
New model |
Description |
2H07 |
CC-RM85 |
Receiver Module, 2-Ch, ST, 850nm, MM |
2H09 |
CC-RX13 |
Receiver Module, 2-Ch, ST 1300nm, MM/SM |
|
MCCC Input/Output Modules:
Legacy model |
New model |
Description |
2P02 |
CC-I |
Input Module, 2-Ch, Dry Contact |
2K02 |
CC-O |
Output Module, 2-Ch, Relay |
|
MCCC Power Supply options:
Model |
Description |
2A06 |
Power Supply, 85 to 240VAC, 50/60Hz, or 85 to 140VDC |
2A16 |
Power Supply, 85 to 240VAC, 50/60Hz, or 85 to 140VDC, w/ diagnostics |
2A08 |
Power Supply, 24VDC |
2A18 |
Power Supply, 24VDC, w/ diagnostics |
|
|
|
 |
FOT/FOR-CC Digital Data Link |

|
Cost effective small package
The FOT-CC fiber optic transmitter and FOR-CC fiber optic receiver are deigned to transmit contact closure data over long distances. The FOT-CC transmitter provides a closed contact signal to the FOR-CC receiver, which activates a single pole double throw (SPDT) relay. They provide ground loop isolation and can be used with 50/125 to 200/230 µm fiber optic cable. The DIN-Rail housings of theses modules facilitate quick and easy mounting on industry standard hardware.
Applications
Remote switch monitoring
Remote relay / solenoid operation |
Features and Benefits:
- Transmission distances up to 5000 meters (16,400 ft.)
- Compact DIN-Rail mounting
- Dry contact input from devices such as push buttons, limit switches and relays
- Form-C relay output (UL/CSA 0.6A/125Vac 2A/30Vdc)
- Compatible with ST Fiber Terminations
- 24 Vdc powered, matching 115/230Vac power supply available
|
Selection guide
Data sheet |
Description |
Input/Output type |
Optical connector |
FOT-CC 850 MM |
Fiber Optic Transmitter – Contact Closure, 850 nm, Multi-mode |
Dry contact input |
ST |
FOT-CC 1300 MM |
Fiber Optic Transmitter – Contact Closure, 1300 nm, Multi-mode |
Dry contact input |
ST |
FOT-CC 1300 SM ST |
Fiber Optic Transmitter – Contact Closure, 1300 nm, Single Mode, Standard Power, |
Dry contact input |
ST |
FOR-CC 850 MM |
Fiber Optic Receiver – Contact Closure, 850 nm, Multi-mode |
Form-C relay output |
ST |
FOR-CC 1300 MM/SM |
Fiber Optic Receiver, Contact Closure, 1300 nm, Multi-mode or Single Mode |
Form-C relay output |
ST |
PSM-CC |
Power supply, 120VAC to 24VDC |
100-250VAC Input / 24VDC @ 200mA output |
N/A |
|
Theory of operation:
The following chart indicates how the output relay contacts will operate on the FOR-CC provided the input contacts on the FOT-CC are wired such that they are closed in a normal operating state and open in a failure mode:
Condition |
FOR-CC output relay state |
1. Normal condition, input closed |
Engergized |
2. Normal condition, input open |
De-energized |
3. Loss of power at TX |
De-energized |
4. Loss of power at RX |
De-energized |
5. Fiber loss (or disconnected) |
De-energized |
6. Component failure at TX |
De-energized |
7. Component failure at RX |
De-energized |
|
|
|
 |
|