ACTIONI/Q®
Q106 AC Powered DC Input Limit Alarm |
Provides Relay Contact Closures at a Preset DC Input Level.
|
Features: |
- Field Configurable Input Ranges
- TouchCALTM Technology
- Setpoints Programmable
HI or LO and Failsafe or Non-Failsafe
- DIN Rail Mounting
with IQRL
- Universal AC Power
85 to 265 VAC
- 24VDC Transducer Excitation
- SnapLocTM Plug-in
Terminals
- ASIC
Technology for Enhanced Reliability
|
 |
|
|
 |
 |
 |
 |
|
Description
The ActionI/Q model Q106 is
a DIN rail mount, DC voltage
or current input limit alarm
with dual setpoints and two
contact closure outputs. The
field configurable input and
alarm functions offer flexible
setpoint capability. Input voltage
spans from 10mV to 200V and
input current spans from 1mA
to 100mA can be field configured.
Bipolar inputs are also accepted.
The
Q106 is configurable as a single
or dual setpoint alarm, with
HI or LO trips and failsafe
or non-failsafe operation. Also
included are adjustable deadbands
(up to 100% of full scale input)
for each setpoint, a 24VDC voltage
source (isolated from line power)
for transducer excitation, and
a universal AC power supply
which accepts any voltage between
85 and 265VAC.
TouchCAL
Technology
Action has simplified setpoint
calibration. Using a pushbutton
instead of potentiometers, improvements
in calibration resolution
and reliability are realized
due to the elimination of the
potentiometers' mechanical variability.
For
calibration, simply input the
signal level of the desired
trip and press the pushbutton
to store it in non-volatile
memory. Deadband is entered
the same way with another pushbutton
press to store.
Diagnostic
LEDS
The Q106 is equipped with three
front panel LEDs. The green
LED is a dual function LED labeled
IN, which indicates line power
and input signal status. Active
AC power is indicated by the
illuminated LED. If this LED
is off, check AC power and wiring
connections. If the input signal
is 7% above or below the configured
input range the green LED will
flash at 8Hz or 4Hz, respectively.
The
two red LEDs indicate the relay
state of each setpoint. An illuminated
red LED indicates the tripped
condition for the respective
setpoint.
Output
The Q106 is equipped with two
SPDT (form C) relays, rated
at 120VAC or 28VDC at 5 amperes.
Each of these relays is independently controlled by the field
configurable setpoint and deadband.
|
 |
Operation
The Q106 limit alarm setpoints
can be configured for HI or
LO, failsafe or non-failsafe
operation. Each of the setpoints
has a respective HI or LO deadband.
In a tripped condition, the
setpoint is exceeded and the
appropriate red LED will illuminate.
The trip will reset only after
the process falls below the
HI deadband or rises above the
low deadband (see Figure 1).
For proper deadband operation,
the HI setpoint must be set
above the LO setpoint. In failsafe
operation, the relay is energized
when the process is below the
HI setpoint or above the LO
setpoint (opposite for non-failsafe).
In the failsafe mode, a power
failure results in an alarm
state output.
Dynamic
Deadband
Circuitry in the Q106 prevents
false trips by repeatedly sampling
the input. The input must be
beyond the setpoint for 100
milliseconds, uninterrupted,
to qualify as a valid trip condition.
Likewise, the input must fall
outside the deadband and remain
there for 100 milliseconds to
return the alarm to an untripped
condition. This results in a
"dynamic deadband"
-based on time- in addition
to the normal deadband.
Configuration
Unless otherwise specified,
the factory presets the Model
Q106 as follows:
Input:
|
 |
Current |
Range:
|
|
0-20mA |
Output:
|
|
Dual,
SPDT |
Trip:
|
|
A:
HI, B: LO |
Failsafe:
|
|
No |
Deadband:
|
|
A,
B: 0.25% |
The AC power input accepts any
AC source between 85 and 265VAC.
Note: An I/QRail is required
to power the modules. See ordering
information.
For
other I/O ranges, refer to Table
1 and Figure 5. Reconfigure
switch SW1 for the desired input
type, range and function.
|
|
|
 |
 |
 |
|
 |
 |
 |
 |
|

Figure
1: Limit alarm operation and
effect of deadband
WARNING:
Do not change switch settings
with power applied. Severe damage
will result!
1.
With the module removed from
the rail and not powered, snap
off the face plate by lifting
the right edge away from the
heat sink. Note the input switch
(SW1) is located under the face
plate. Set positions 9 &
10 for voltage or current input
(see Table 1).
2.
Set positions 1 through 4 of
input range switch "SW1"
for the desired input range
(see Table 1).
3.
Set position 5 of input range
switch "SW1" to ON
(closed) for unipolar (e.g.,
zero based, 0-20mA) range or
OFF (open) for bipolar (e.g.
-100% offset, -20 to 20mA) range.
4.
Set positions 6 and 7 of input
range switch "SW1"
to ON for a HI trip setpoint
or OFF for a LO trip setpoint.
5.
Set position 8 of input range
switch "SW1" to ON
for non-failsafe operation or
OFF for failsafe operation (e.g.,
alarm trips on power failure).
Calibration
1. After configuring the DIP
switches, connect the input
to a calibrated DC source and
apply power. Refer to the terminal
wiring in the specifications
section.
Note:
For best results, calibration
should be performed in the operating
environment, mounted on a DIN
rail, allowing at least one
hour for thermal equilibrium
of the system.
2.
After applying power to the
unit all three LEDs will flash
for approximately 10 seconds.
Adjust the input signal level
for the Relay "A"
setpoint. The green LED should
be on. Press and hold the CAL
button for four seconds (until
the red LED starts flashing)
to enter the calibration mode.
The green LED will be on and
the red Relay "A"
LED will be be flashing.
NOTE:
If the green LED is flashing
, the input is out of range
(i.e. 7% above or below the
configured range). Check to
make sure the input signal is
within the DIP switch configuration
range. Double check the DIP
switch settings.
3.
Setpoint "A": Input
the desired trip level for Relay
"A" and press the
CAL button. The green LED and
the red Relay "A"
LED will be flashing. Note that
the green LED will stop flashing
when the input drops below a
high setpoint or rises above
a low setpoint.
|
 |
4.
Deadband "A": For
minimum deadband (approximately
0.25%), press and hold the CAL
button for 4 seconds. For high
setpoints, lower the input level
to the desired deadband point
and push the CAL button. For
low setpoints increase the input
level (green LED turns off)
to the desired deadband level
and push the CAL button. The
green LED will be on and the
red Relay "B" LED
will be flashing.
5.
Setpoint "B": Input
the desired trip level for Relay
"B" and push the CAL
button. The green and the red
Relay "B" LED will
be flashing. Note that the green
LED will stop flashing when
the input drops below a high
setpoint or rises above a low
setpoint.
6.
Deadband "B": For
minimum deadband (approximately
0.25%), press and hold the CAL
button for 4 seconds. For high
setpoints lower the input level
(green LED turns off) to the
desired deadband point and push
the CAL button. For low setpoints
increase the input level to
the desired deadband level and
push the CAL button. The green
LED will be on and both the
red LEDs will be flashing.
7.
Press the CAL button once again
to exit the calibration mode.
Check the setpoint and deadband
to validate calibration.
Relay
Protection and EMI Suppression
When switching inductive loads,
maximum relay life and transient
EMI suppression is achieved
by using external protection
(see Figures 2 and 3). Place
all protection devices directly
across the load and minimize
lead lengths. For AC inductive
loads, place a properly rated
MOV across the load in parallel
with a series RC snubber. Use
a 0.01 to 0.1mF pulse film capacitor
(foil polypropylene recom- mended)
of sufficient voltage, and a
47 ohm, 1/2W carbon resistor.
For DC inductive loads, place
a diode across the load (PRV
> DC supply, 1N4006 recommended)
with (+) to cathode and (-)
to anode (the RC snubber is
an optional enhancement).
Table
1: Q106 Input Range Switch

|
|
|
 |
 |
 |
|
 |
|
 |
 |
 |
 |
|
Specifications
Voltage Input: |
Range:
10mV to +200V; Impedance:
>100K ohms
Overvoltage: 200V rms,
max.
|
Current
Input: |
Range:
1mA to +100mA; Impedance:
20 ohms, typical
Overcurrent: 170mA rms,
max. Overvoltage: 60VDC
(self-resetting fuse)
Common Mode (Input to
Gnd): 1800VDC, max.
|
LED
Indicators: |
Input
(Green):
>110%
input: 8Hz flash
<10%
input: 4Hz flash
Setpoint (Red):
Tripped: Solid red
Safe: Off
|
Limit
Differential (Deadband): |
>50mV/5mA:
0.25% to 100% of span
<50mV/5mA: 1% to
100% of span
|
Response
Time: |
Dynamic
Deadband:
Relay
status will change when
proper setpoint/process
condition exists for
100msec.
Normal Mode (analog
filtering): <250mSec,
(10-90%)
|
Setpoints: |
Effectivity:
Setpoints are adjustable
over 100% of the selected
input span. Repeatability
(constant temp.):
>50mV/5mA:
0.1% of full scale
<50mV/5mA:
0.2% of full scale
|
Stability: |
Temperature:
+0.05% of full scale/
C, max.
|
Excitation
Voltage: |
24VDC,
20mA, maximum
|
|
 |
Common
Mode Rejection: |
DC
to 60Hz: 120dB
|
Isolation: |
1800VDC
between contacts, input
and power
|
ESD
& Transient Susceptibility: |
Meets
IEC 801-2, Level 3 (8KV)
|
Humidity
(Non-Condensing):
|
Operating:
15 to 95% @ 45 C
Soak: 90% for 24hours
@ 65 C
|
Temperature
Range: |
Operating:
0 to 55 C (32 to 131
F)
Storage: -25 to 70 C
(-13 to 158 F)
|
Power: |
2.5W
max.,100 to 240VAC +10%,
50Hz -400Hz
|
Relay
Contacts: |
2
SPDT (2 form C) Relays;
1 Relay per setpoint
Current Rating (resistive)
120VAC:5A; 240VAC: 2A;
28VDC: 5A
Material: Gold flash
over silver alloy
Electrical Life:105
operations at rated
load
Note: External relay
contact protection is
required for use with
inductive loads.
Mechanical Life: 107
operations
|
Wire
Terminations: |
Screw
terminations for 12-22
AWG
|
Weight: |
0.56
lbs
|
Agency
Approvals: |
UL
recognized per standard
UL508 (File No E99775)
CE EN61326, EN61010-1
|
|
Ordering
Information |
Models
& Accessories |
Specify
(model number) |
-
Q106-0000
- Specify
I/QRail type and quantity
(required)
- Accessories:
(see Accessories)
- Optional
Custom Factory Calibration:
Specify C620 with desired
input, setpoint and
deadband.
|
Accessories |
ActionI/Q
series modules mount on
standard TS32 (model MD02)
or TS35 (model MD03) DIN
rail. In addition, the
following accessories
are available: |
MD02
TS32 DIN rail
MD03 TS35 x 7.5
DIN rail
IQRL-2002 2 Position
I/QRail & DIN rail
IQRL-2004 4 Position
I/QRail & DIN rail
IQRL-2008 8 Position
I/QRail & DIN rail
|
 |
Terminal |
Connection |
Terminal |
Connection |
A1 |
Relay
A, N.O |
C4 |
24
VDC Excitation |
A2 |
Relay
A, Common |
C5 |
Input
(-) |
A3 |
Relay
A, N.C. |
C6 |
Input
(+) |
A4 |
Relay
B, N.O. |
P1 |
AC
Power (Hot) |
A5 |
Relay
B, Common |
P2 |
Not
Used |
A6 |
Relay
B, N.C. |
P3 |
Not
Used |
C1,
C2, C3 |
Not
Internally Connected |
P4 |
AC
Power (Neutral) |
|
 |
Dimensions
|
|
|
 |
 |
 |
|
|
|