Action ULTRA SLIMPAK® G118-0002 DC Powered RTD Input Limit Alarm

Provides Relay Contact Closures at a Preset RTD/Resistance Input Level.


Features:
  • Programmable HI or LO, Failsafe or Non-failsafe
  • Field Configurable Ranges for Platinum, Nickel and Copper RTDs
  • Ultra Slim Housing for High Density Installations
  • LED Trip and Input Indicators
  • Flexible Power Supply Accepts 9 to 30 VDC
  • ASIC Technology for Enhanced Reliability
  • RoHS Compliant

G118-0002

Description
The Ultra SlimPak G118 is a DIN rail mount, RTD input limit alarm with dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. There are up to eight temperature ranges available for each RTD type to ensure accuracy and maximize setpoint resolution.

The G118 is configurable as a single or dual setpoint alarm, with HI or LO trips and failsafe or non-failsafe operation. Also included are adjustable deadbands (0.25 to 5% of full scale input) for each setpoint and a flexible DC power supply which accepts any voltage between 9 and 30VDC.

Operation
The field configurable G118 limit alarm setpoints can be config- ured for HI or LO, failsafe or non-failsafe operation. Each of the setpoints has a respective HI or LO deadband. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the LO deadband (see Figure 1). For proper deadband operation the HI setpoint must always be set above the LO setpoint. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.

Click here for the complete information in .pdf format

 

 
 
CTH Controls Inc.   CTH Controls Inc.
6-1500 Upper Middle Rd. W. Suite 220
Oakville, ON, Canada, L6M 0C2
Phone: 905-792-6829
Toll Free: 1-888-550-6829
Fax: 905-792-6902
sales@cthcontrols.com
  arrow Line Monitoring arrow Contact Us  

For Secure Payments
Mastercard Visa
<empty> <empty> <empty>
<empty>
PAYPAL
PAYMENT
GUIDE
<empty>
<empty> <empty> <empty>
  arrow Products arrow Supplier Inquiry  
  arrow Services arrow ISO Certification  
  arrow Support arrow Return Policy  
  arrow Web Store arrow Careers  
  arrow About Us arrow Line Card  
© Copyright 1998-2017, CTH Controls Inc. All rights reserved